Optimized Power Supplies Beget Superior Data-Center Efficiency
Data centers are conspicuous consumers of power. Power-supply design that maximizes efficiency can deliver big payoffs.
Don Tuite
ED Online ID #20732
March 12, 2009
Copyright © 2006 Penton Media, Inc., All rights reserved. Printing of this document is for personal use only.
Reprints
LLarge data centers devour huge amounts of electrical power (see
“Energy-Hungry IT Centers See Hope In Digital Power”). At the heart of efforts to
reduce wasted energy, power-supply makers offer a host of ways
to minimize their contributions to the problem.
In broad terms, the challenge is to deliver power to hundreds of
servers’ processors at very low voltage levels from multiphase ac
mains. The processors have three power rings—logic, memory, and
I/O—all requiring very precisely regulated voltages on the order of
1 V, regulated to a precision of one one-hundredth of a volt.
The processor loads are highly variable, depending on how hard
the processors are working, that is, how many gates are switching.
Those loads vary from milliamps to tens of amps, with transient
demands of hundreds of volts per microsecond.
A complicating factor is that the voltages to the different power
rings on the processors must be managed in terms of regulation as
well as sequencing. They must be applied and removed in a fixed
order, with precise timing. The challenge is to create an efficient
power-distribution network that can convert power from the grid
to those dynamic low-voltage loads.
Five power distribution alternatives for data centers are either
in use or under discussion (Fig. 1). But which is most optimal
in terms of overall efficiency? Debate continues, but an interesting
analysis, “AC vs. DC Power Distribution for Data Centers” by
American Power Conversion’s Neil Rasmussen, provides a methodology
for analysis.
Approaches a and b in Figure 1 represent, respectively, the
configurations generally used in North America and the rest of the
world for data centers. Approach c represents the configuration
used in telecom central offices.
In the North American data-center configuration, the mains
power goes through an uninterruptible power supply (UPS) and a
transformer-based power-distribution unit (PDU), and then to the
server rack. In the rest of the world, where ac mains voltages are
higher, there’s no need for the PDU.
The UPS provides pre-regulated ac power, either from the ac
line, or, when the utility power drops out, from a battery bank. Its
first stage is simply an ac-dc rectifier whose unfiltered output is
applied to the battery bank. Its second stage is an inverter. The ac
inverter feeds the PDU, which provides power factor correction
and steps up the ac voltage for distribution around the data center.
Inside each equipment cabinet, a front-end converter rectifies the
ac and steps it down for distribution across the backplane.
In the telco central office, the UPS has historically comprised a
large, 48-V lead-acid array to provide the mandated “five nines”
(99.999%) availability. Therefore, 48 V is distributed directly to
backplane busses in equipment cabinets.
Challenging the traditional approaches, the configurations in
d and e are based on producing high dc voltages at the front end/
UPS and busing that are around the data center, with proportionally
lower I2R losses. The version in e would require the last stepdown
to 48 V to occur in the equipment cabinets. Meanwhile, the
version in d would use a common step-down converter and allow
for conventional 48-V distribution on backplanes.
By discounting certain assumptions in other studies that favor
the high-voltage dc concepts, Rasmussen’s analysis essentially
concludes that the conventional “rest of the world” approach is
optimum. Read the analysis yourself and decide what you think.
Inside the equipment cabinets, the common model is the intermediate
bus architecture (IBA). The IBA takes that nominal 48-V
dc backplane voltage and applies it to a step-down converter on
each board, often in the form factor of a fractional “brick” (Fig.
2). This brick then isolates and transforms the 48 V to a somewhat
regulated intermediate bus voltage. This voltage supplies a number
of point-of-load (POL) dc-dc converters that step-down and
tightly regulate the voltages for critical ICs. For the sake of efficiency
and control, these are always switch-mode converters.
To simplify this explanation, we’ve been treating the intermediate
bus voltage provided by the dc-dc brick regulators as if it
were standardized at 12 V. In actuality, it might be 12, 8, or 5 V
dc. It depends on the system design. A higher bus voltage suffers
less from I2R losses, but the efficiency of each simple dc-dc buck
regulator at each POL decreases with the ratio of voltages it has to
drop. Thus, the choice of bus voltage involves some tradeoffs.
FLATTENING EFFICIENCY CURVES
Even though improving POL efficiency results in small energy
savings, the effects add up. In fact, they actually compound as
they’re reflected back through the supply chain (Fig. 3).
In the past, power-supply efficiency numbers on data sheets
referred to peak efficiency, which usually happened between 50%
and 80% of rated load. Actual efficiency would fall off slightly at
full load and sometimes dramatically at loads around 20% or so.
Recent standards worldwide recognize that loads are variable and
call for high efficiencies (80% and more) across a range of loads
from 20% to 100%.
Achieving and improving efficiency across the full load range
has become a point of differentiation among power-supply manufacturers
at all power levels, with the application of proprietary
techniques and considerable squabbling over patents. Broadly,
efficiency-boosting techniques include synchronous rectification,
cycle skipping, and multiple phases and phase shedding.
Continue to page 2
Synchronous rectification replaces the flywheel diode with
a power FET. In more detail, a basic buck or boost converter
requires only a single switching transistor, plus a rectifying diode.
The problem with that, though, is the losses related to current
times forward drop and reverse recovery time. Schottky diodes
help, with their relatively low forward-voltage drop and good
reverse-recovery characteristics. But what’s really needed for efficiency
is another MOSFET switch instead of a silicon diode.
The tradeoff is added complexity, both in terms of parts count
and timing control. The need for added timing control arises
because there must be a certain amount of dead time between one
switch opening and the other closing.
Also, that dead time requires some sort of diode to conduct
between the time the top switch opens and the bottom switch
closes. This can be handled by the intrinsic body diode in the
MOSFET or by an external Schottky.
Let’s take synchronous switching one step further. In highpower
ac-dc flyback-topology converters, the quasi-resonant or
valley switching power supply varies switching frequency with
input voltage changes to switch the MOSFET at the lowest point,
or the valley, of the switching-MOSFET drain voltage.
Cycle skipping improves efficiency at light loads. In skip
mode, a new cycle is initiated only when the output voltage
drops below the regulating threshold. The switching frequency is
proportional to the load current. With synchronous rectification,
care must be taken to open the switch when the current through
the inductor reverses so the MOSFET’s body diode blocks the
reverse current.
Multiple phases and phase shedding involve ganging multiple
low-current switching converters. These run at a common
switching frequency, but with their clock phases shifted.
Paralleling the output of several switching regulators provides
increased current capacity, along with other advantages. Each
parallel switcher in a multiphase dc-dc converter operates at a
relatively low frequency. However, when combined, they produce
the responsiveness and regulation performance of a single-phase
very high switching-frequency converter without the switching
losses associated with higher frequencies. Also, by staggering the
phases, the inherent output ripple is smoothed out.
So far, so good. Things get really interesting with multiphase
switching regulators, though, when shedding phases to handle
light loads with higher efficiency. At light loads, it makes sense
to shut down some phases, because the efficiency of individual
converters is greater at higher loads. As the total load increases,
dormant phases can be brought back on line. The tricky part here
lies in phase synchronization and balancing—adjusting the relative
phase angles on the fly.
For certain situations, it’s better to drive all clock phases in
sync. In some of its dc-dc regulators, Primarion (now part of Infineon)
does just that. The chips can switch between two modes: one
“normal,” the other called Active Transient Response (ATR).
In normal mode, phase pulses are evenly distributed to minimize
the combined ripple. In ATR, the clocks to all phases are
time-aligned, effectively paralleling the inductors to reduce total
inductance and increase transient ramp time. This technique has
been applied to POLs with eight phases to deliver di/dt rates in
excess of 800 A/µs at the inductors and over 1500 A/µs at the
output capacitor.
DIGITAL POWER
Five or so years ago, there was a curious debate about whether
it was better to close the control loop in switch-mode power
supplies in the analog domain or the digital domain. Eventually,
everyone realized that was the wrong debate, that “digital” ought
to mean telemetry and a programmable bus (with maybe the parallel
possibility of programming some parameters with external
resistors or by pin-strapping).
Those goals could be achieved regardless of the implementation
of the control loop. It’s perfectly possible to put an analog
loop inside a digital “wrapper.” (There’s still a debate on the digital
side as to whether control is better implemented via a microcontroller
or a state machine.)
There are a number of advantages to a two-way control and
monitoring bus. Downstream, it enables rapid reconfiguration.
Used bidirectionally and coupled with a graphical user interface
(GUI), it provides a way to manage the control loop in-circuit
(Fig. 4). Upstream, the two-way control and monitoring bus
facilitates system diagnostics and prediction of potential failures.
Through temperature monitoring, it provides a way to manage
multiple server fans to avoid hot spots in cabinets.
With the market clearly in favor of some kind of control bus, the
question came down to implementation—whether an industrystandard
bus was better, or whether proprietary buses would provide more innovation. It’s the classic opensource,
closed-source debate. As it worked
out, the debate led to a legal situation that
stalemated development for over a year.
I’ve been told privately that those issues
will resolve themselves shortly, perhaps
as soon as the 2009 APEC conference, or
shortly after. Unfortunately, that news will
be too late for this report. But Electronic
Design will report on it online as soon as
it happens.
Continue to page 3
In the meantime, the best way to explain
the situation is by looking first at PMBus,
the open-standard digital power-management
protocol for communication between
the power converter and other devices.
PMBus defines the transport and physical
interface. It additionally provides a command
language. It doesn’t, though, address
communication between one power source
and another.
The transport layer is based on the
SMBus (System Management Bus) extension
of the I2C serial bus with packet error
checking and host notification features. In
lieu of polling, it adds a third signal line
that enables slave devices such as POL
converters to interrupt the system host/bus
master. In addition, there are hardwired
signals for turning slave devices on and
off and for write-protecting memory-held
data. Also included are packet specifications
and a power-control-specific command
set.
For a more detailed explanation of
PMBus and its relation to power in the
data center, see “PMBus Takes Command
of Data Center Power Issues” by Intel’s
Brian Griffith
in Electronic Design’s sister publication,
Power Electronics Technology.
A strongly competitive proprietary
approach has been Power-One’s Z-Bus.
PMBus places a certain coding and computational
overhead on the system controller.
Z-Bus uses a separate controller that
can handle many POLs.
The proprietary Z-system preceded
PMBus and operates differently. It relies
on an external controller that gets its commands
via an I2C interface and communicates
with Z-POLs over a single synchronization/
data line called the Z-Bus. The
Z-Bus synchronizes multiple Z-POLs to a
master clock in the manager chip and carries
bidirectional data between POLs and
the dynamic power management (DPM).
The Z-system offers multi-POL control
over output voltage, output tracking and
sequencing, switching frequency, interleaving,
and active digital current sharing.
Beyond voltage regulation, programmable
parameters include output tracking and
sequencing, switching frequency, interleaving,
feedback-loop compensation, and
active digital current sharing with multiple
Z-POL converters. Among the programmable
protection features are output overcurrent
and overvoltage, input undervoltage,
power-good signal limits, and fault management. Real-time reporting includes
output voltage and current and POL temperature.
This can all be programmed via a
highly intuitive GUI.
In late 2007, the race between Z-Bus
and PMBus entered a new phase when a
jury agreed with Power-One that any use
of PMBus to control POLs infringed Power-
One’s patents. Abruptly, the number of
new product announcements about digital
POLs for IBA applications almost dried
up—but not completely.
Last year, it appeared that Ericsson
Power Modules might have sidestepped
the patent problem by moving PMBus
control to the formerly “dumb” bricks and
tightening up their regulation, relieving the
POLs of that burden. Specifically, Emerson
introduced new fractional bricks in the
standard quarter-brick footprint that could
be set via PMBus for output levels between
8.5 and 13.5 V, to ±2% precision, with a
current capacity up to 33 A at 12 V. Thanks
to the digital control loop, typical efficiency
is 96% at half load, and that efficiency is
nearly flat out to full load.
Physically, Ericsson added a separate
header for the communication bus at the
opposite end from a brick’s standard input/
output pins. The bus includes pins that
allow two of these bricks to load-share
while automatically phase-interleaving
their switching signals to minimize conducted
interference. Whether that still
infringes on Power-One’s patent claims is
still moot, but it was the only interesting
new product development on the PMBus
front during the past year.
OTHER PLAYERS
Companies that introduced PMBusbased
POLs before the Texas jury reached
its decision for Power-One in November
2007 included Intersil, Linear Technology,
Maxim Integrated Products, Primarion/
Infineon, and Texas Instruments. Additional
players in the field took a hard look
at the broadness of Power-One’s claims.
In 2005, Zilker Labs (recently acquired
by Intersil) introduced a line of POLs that
use state-machine control, rather than a
microcontroller. (For a complete discussion
of the methodology’s merits, see
“PMBus Controller Takes A State-Machine
Approach.”) For designers,
the real appeal of the Zilker/Intersil
approach may be ease of use—in particular,
how simple it is to use multiple Zilker
controllers in the same circuit.
The controllers can be individually programmed
(pin-strap, resistor, or SMBus)
for regulated output voltage, turn-on delay,
and output-voltage ramp rate. SMBus programming
provides the highest precision,
but simply using a pair of resistors allows
the output to be positioned between 0.6 and
5.5 V in 10-mV steps. Alternatively, simple
pin-strapping (three pins: low, high, or
open) enables the output voltage to be set to
any of nine values between 0.6 and 5 V.
For power sequencing, a group of Zilker’s
POL devices might be configured to
power up in a predetermined order by issuing
PMBus commands to assign preceding
and succeeding devices in the sequencing
chain. Yet a simpler approach would use
Zilker’s patented autonomous sequencing
mode, in which case no I2C/SMBus host
would be needed.
All that’s necessary is that the I2C pins
be interconnected for each device. In that
case, sequence order is determined on the
basis of each device’s bus address. Phasespreading
is possible when all converters
are synchronized to the same switching
clock. In that case, the phase offset for each
chip is determined by its device address,
where phase offset = device address × 45°.
Radically different from all other players,
Vicor’s Factorized Power approach,
introduced in 2003, is based on very efficient
nonregulating isolated POL-like
chips while providing upstream regulation.
Advantages include a higher bus voltage,
with low I2R losses and voltage drop.
Continue to page 4
Also, the ability to move the bulk capacitors
that store the energy needed to handle the load’s transient current demands
from the output of the POL upstream to
the input reduced the amount of capacitance
needed by the square of the POL’s
step-down ratio. Finally, it provides the
ability to precisely control the load voltage
through the isolation barrier without long,
noise-sensitive feedback lines or opto- or
magnetic couplers.
Factorized power introduces its own terminology.
Isolated voltage transformation
modules (VTMs) are at the load, while preregulator
modules (PRMs) can be found
upstream. Load regulation is performed
using feedback to the upstream PRM. The
PRM adjusts the factorized bus voltage to
maintain the load voltage in regulation.
The key to this is the VTM’s function
as a current transformer. It multiplies the
current (or divides the voltage) by a “K”
factor. This takes place with essentially a
100% transformation duty cycle, so there’s
no loss of efficiency at high values of K.
Thus, the bus voltage can be (and is) greater
than 12 V. In fact, it’s limited only by
safety concerns.
The bulk capacitance at the VTM input
reflects itself at the POL with a gain
equal to the square of the VTM current
gain. Only very small amounts of ceramic
bypass capacitance, effective over a short
time scale of less than a microsecond, are
needed at the load.
PRMs employ a ZVS buck-boost control
architecture. One can operate with
input voltages from 1.5 to 400 V, and step
up or step down over a 5:1 range, with a
conversion efficiency up to 98%. In normal
configurations, the output voltage is
approximately equal to the input voltage:
48 V unregulated to 48 V regulated. One
PRM can put out up to 300 W, and VTMs
and PRMs may be paralleled for higher
output power.
A VTM employs a zero-voltage switching
and zero-current switching (ZCS/ZVS)
topology that Vicor calls a sine amplitude
converter, or SAC (Fig. 5). The power train
is a low-Q, high-frequency, controlled
oscillator with high spectral purity and
common-mode symmetry, resulting in
practically noise-free operation.
The control architecture locks the operating
frequency to the power-train resonant
frequency, optimizing efficiency and minimizing
output impedance by effectively
canceling reactive components. ROUT, an
equivalent resistance that summarizes all
losses in the VTM, can be as low as 0.8 mO
from a single VTM. If that isn’t low enough,
or if more power is required, VTMs can be
paralleled for current sharing. The SACbased
VTM is, for the most part, a linear
voltage/current converter with a flat output
impedance up to about 1 MHz.
The secondary current in a SAC VTM is a
virtually pure sinusoid. The very low, essentially
non-inductive output impedance of the
VTM allows an almost instantaneous
response to a 100% step change in load current.
Because there’s no internal regulation
circuitry in a VTM, and none of the attendant
loop delays and stability issues, no
internal control action is required to respond
to the change in load. The internal ASIC
controller simply continues controlling and
synchronizing the operation of the switches
to maintain operation at resonance.
|